3 4 Cores Armoured Underground PVC Medium Voltage Power Cable
3 4 Cores Armoured Underground PVC Medium Voltage Power CableConstruction :Conductor: Solid & stranded copper wire class1&2 acc.to IEC60228 Solid & stranded Alum
3 4 Cores Armoured Underground PVC Medium Voltage Power CableConstruction :Conductor: Solid & stranded copper wire class1&2 acc.to IEC60228 Solid & stranded Alum
3 4 Cores Armoured Underground PVC Medium Voltage Power Cable
Construction :
Conductor: Solid & stranded copper wire class1&2 acc.to IEC60228
Solid & stranded Aluminium wire
Insulation:PVC Compound
Filler: PVC Compound
Sheath:PVC Compound
Sheath Color:White ,Black,Grey
Techical Data :
Standard:IEC 60502-1 / VDE 0276 /NT88-22
Fixed installed: -15ºC up to 70ºC
At short circuit of max.5s up to 160ºC
Nominal Voltage : 600/1000V
Min inner bending radius:
Single coe:15D
Multi core:12D
Behaviour in fire:
Flame retardant cable acc.to IEC60332-1
Application:
PVC power cable for static outdoor application (with protection against direct UV-irradiation), in ground, in water, within facilities, in cable canals, in concrete, in conditions where heavier mechanical loads and specially tensile strains, are not expected. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and in other electric plants, same as for connection of signalling devices in industry, traffic and similar.
Technical Parameters:
No.of cores x Nominal section area | Nominal Construction of conductor | Nominal Insulation thickness | Nominal Sheath thickness | Nominal Overall diameter | Nominal Cable weight | Max.Resistance of conductor at 20ºC |
No.X mm² | No.X mm | mm | mm | mm | kg/km | <=(Ω/km) |
Three core PVC Power Cables CU/XLPE/PVC( AL/XLPE/PVC ) | ||||||
3x1.5 | 2x 1.38 | 0,7 | 1,8 | 11.3 | 130 | 12,10 |
3x2.5 | 7 x 0,67 | 0,7 | 1,8 | 11.8 | 170 | 7,41 |
3x4.0 | 7 x 0,85 | 0,7 | 1,8 | 13.1 | 230 | 4,61 |
3x6.0 | 7 x 1,04 | 0,7 | 1,8 | 13.9 | 305 | 3,08 |
3x10 | 7 x 1,35 | 0,7 | 1,8 | 17.5 | 450 | 1,83 |
3x16 | 7 x 1,70 | 0,7 | 1,8 | 18.2 | 615 | 1,150 |
3x25 | 7 x 2,14 | 0,9 | 1,8 | 19.1 | 870 | 0,727 |
3x35 | 7 x 2,52 | 0,9 | 1,8 | 21.1 | 1155 | 0,524 |
3x50 | 19 x 1,78 | 1,0 | 1,8 | 23.8 | 1530 | 0,387 |
No.of cores x Nominal section area | Nominal Construction of conductor | Nominal Insulation thickness | Nominal Sheath thickness | Nominal Overall diameter | Nominal Cable weight | Max.Resistance of conductor at 20ºC |
No.X mm² | No.X mm | mm | mm | mm | kg/km | <=(Ω/km) |
Four core PVC Power Cables CU/XLPE/PVC( AL/XLPE/PVC ) | ||||||
4x1.5 | 2x 1.38 | 0,7 | 1,8 | 12.1 | 150 | 12,10 |
4x2.5 | 7 x 0,67 | 0,7 | 1,8 | 13.2 | 200 | 7,41 |
4x4.0 | 7 x 0,85 | 0,7 | 1,8 | 14.9 | 275 | 4,61 |
4x6.0 | 7 x 1,04 | 0,7 | 1,8 | 16.1 | 370 | 3,08 |
4x10 | 7 x 1,35 | 0,7 | 1,8 | 18.6 | 560 | 1,83 |
4x16 | 7 x 1,70 | 0,7 | 1,8 | 20.2 | 795 | 1,150 |
4x25 | 7 x 2,14 | 0,9 | 1,8 | 21.8 | 1130 | 0,727 |
4x35 | 7 x 2,52 | 0,9 | 1,8 | 24.1 | 1515 | 0,524 |
4x50 | 19 x 1,78 | 1,0 | 1,9 | 27.5 | 2010 | 0,387 |
4x70 | 19 x 2,14 | 1,1 | 2,0 | 31.7 | 2860 | 0,268 |
4x95 | 19 x 2,52 | 1,1 | 2,1 | 35.4 | 3870 | 0,193 |
4x120 | 37 x 2,03 | 1,2 | 2,3 | 39.2 | 4850 | 0,153 |
4x150 | 37 x 2,25 | 1,4 | 2,4 | 43.8 | 5980 | 0,124 |
4x185 | 37 x 2,52 | 1,6 | 2,6 | 48.7 | 7480 | 0,0991 |
4x240 | 61 x 2,25 | 1,7 | 2,8 | 54.4 | 9735 | 0,0754 |
4x300 | 61 x 2,52 | 1,8 | 3,0 | 59.9 | 12120 | 0,0601 |